2. EXTERNAL DIMENSIONS
YKB/YLM 2nd
Y (HIGH COP)
MEE15K022
T
winning pipe connection size
EP350
ø28.58
ø12.7
e or g or i
Unit model
EP300
Liquid
Gas
f or h or j
T
winning pipe~Outdoor unit
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
     2.T
winning pipes should not be tilted more than 15 degrees from the horizontal plane.  
       Be sure to see the Installation Manual for details of
T
winning pipe installation.
     3.The pipe section before the
T
winning pipe (sections "a", "b", "c" and "d" in the figure) must have at least  
       500mm of straight section (*including the straight pipe that is supplied with the
T
winning pipe).
     4.Only use the
T
winning pipe by Mitsubishi (optional parts).
     5.The detachable leg can be removed at site.
d
c
b
a
ø34.93
ø41.28
ø19.05
ø19.05
CMY
-Y300VBK3
PUHY
-EP300YLM-A1(-BS)
PUHY
-EP400YLM-A1(-BS)
PUHY
-EP300YLM-A1(-BS)
PUHY
-EP1000YSLM-A1(-BS)
Outdoor unit 3
Liquid
Liquid
Gas
Gas
Outdoor unit 2
Outdoor unit 1
T
winning pipe 1~T
winning pipe 2
Indoor unit~T
winning pipe 2
Outdoor
T
winning Kit(optional parts)
Component unit name
Package unit name
PUHY
-EP300YLM-A1(-BS)
PUHY
-EP400YLM-A1(-BS)
PUHY
-EP350YLM-A1(-BS)
PUHY
-EP1050YSLM-A1(-BS)
PUHY
-EP350YLM-A1(-BS)
PUHY
-EP400YLM-A1(-BS)
PUHY
-EP350YLM-A1(-BS)
PUHY
-EP1
100YSLM-A1(-BS)
PUHY
-EP350YLM-A1(-BS)
PUHY
-EP450YLM-A1(-BS)
PUHY
-EP350YLM-A1(-BS)
PUHY
-EP1
150YSLM-A1(-BS)
EP450
EP400
ø28.58
ø12.7
ø15.88
ø15.88
Left view
Front view
Intake
air
Intake
air
Intake
air
T
o indoor unit
T
o indoor unit
Gas
T
winning pipe 2 <optional parts>
b
a
Liquid
T
winning pipe 2 <optional parts>
j
i
Gas
T
winning pipe 1 <optional parts>
d
c
Liquid
T
winning pipe 1 <optional parts>
h
g
f
e
Discharge air
Outdoor unit 1
Outdoor unit 2
Outdoor unit 3
Detachable leg
Note 5*
ø28.58
ø28.58
1650
(60)
740
1750
30
1220
30
1220
1710
PUHY
-EP1000, 1050, 1
100, 1150YSLM-A1 (-BS)
Unit : mm