2 - 131
1. SPECIFICATIONS
YKB/YLM 2nd
Y (HIGH COP)
MEE15K022
Model
PUHY-EP1200YSLM-A1 (-BS)
Power source
3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity
*1
kW
136.0
(Nominal)
kcal/h
117,000
*1
BTU/h
464,000
Power input
kW
42.76
Current input
A
72.1-68.5-66.0
EER
kW/kW
3.18
Temp.
range of
Indoor
W.
B.
15.0~24.0°C (59~75°F)
cooling
Outdoor
D.B.
-5.0~52.0°C (23~126°F)
Heating capacity
*2
kW
150.0
(Nominal)
kcal/h
129,000
*2
BTU/h
511,800
Power input
kW
45.45
Current input
A
76.7-72.8-70.2
COP
kW/kW
3.30
Temp.
range of
Indoor
D.
B.
15.0~27.0°C (59~81°F)
heating
Outdoor
W.B.
-20.0~15.5°C (-4~60°F)
Indoor unit
Total capacity
50~130% of outdoor unit capacity
connectable
Model/Quantity
P15~P250/3~50
Sound pressure level (measured in anechoic room)
dB <A>
67
Sound power level (measured in anechoic room)
dB <A>
87.5
Refrigerant
Liquid pipe
mm (in.
)
19.05 (3/4) Brazed
piping diameter
Gas pipe
mm (in.
)
41.28 (1-5/8) Brazed
Set Model
Model
PUHY-EP350YLM-A1 (-BS)
PUHY-EP400YLM-A1 (-BS)
PUHY-EP450YLM-A1 (-BS)
FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 2
Propeller fan x 2
Air flow rate
m
3
/min
200
320
370
L/s
3,333
5,333
6,167
cfm
7,062
11,299
13,065
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92 x 1
0.92 x 2
0.92 x 2
*3
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Starting method
Inverter
Inverter
Inverter
Motor output
kW
10.5
10.9
12.4
Case heater
kW
-
-
-
Lubricant
MEL32
MEL32
MEL32
External finish
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D
mm
1,710 (1,650 without legs) x 1,220 x 740
1,710 (1,650 without legs) x 1,750 x 740
1,710 (1,650 without legs) x 1,750 x 740
in.
67-3/8 (65 without legs) x 48-1/16 x 29-3/
16
67-3/8 (65 without legs) x 68-15/16 x 29-
3/16
67-3/8 (65 without legs) x 68-15/16 x 29-
3/16
Protection devices
High pressure protection
High pressure sensor, High pressure
switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure
switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure
switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN)
Over-heat protection, Over-current pro-
tection
Over-heat protection, Over-current pro-
tection
Over-heat protection, Over-current pro-
tection
Compressor
-
-
-
Fan motor
-
-
-
Refrigerant
Type x original charge
R410A x 10.3 kg (23 lbs)
R410A x 11.8 kg (27 lbs)
R410A x 11.8 kg (27 lbs)
Control
LEV and HIC circuit
Net weight
kg (lbs)
237 (523)
306 (675)
306 (675)
Heat exchanger
Salt-resistant cross fin & aluminium tube
Salt-resistant cross fin & aluminium tube
Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe, tube-in-tube structure
Copper pipe, tube-in-tube structure
Copper pipe, tube-in-tube structure
Pipe between unit and
Liquid pipe
mm (in.
)
12.7 (1/2) Brazed
15.88 (5/8) Brazed
15.88 (5/8) Brazed
distributor
Gas pipe
mm (in.
)
28.58 (1-1/8) Brazed
28.58 (1-1/8) Brazed
28.58 (1-1/8) Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing
External
WKS94C153
Wiring
WKE94G039
WKE94G040
WKE94G040
Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
Optional parts
Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1)
Indoor: 27°CD.B./19°CW.B. (81°FD.B.
/66°FW.
B.
), Outdoor: 35°CD.B. /24°CW.B. (95°FD.B./75°FW.
B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B.
/6°CW.B.
(45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30Pa, 60Pa/3.1mmH
2
O, 6.1mmH
2
O).
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.