2 - 60
Y
MEE15K022
6. VIBRATION LEVEL
YKB/YLM 2nd
6. VIBRATION LEVEL
[PUHY-P200-500YKB-A1, PUHY-P400-1350YSKB-A1]
* Vibration level varies depending on the conditions of actual installation site.
20cm
10cm
Concrete
Service panel side
Measurement point
Measurement condition
Measurement frequency: 1 Hz-80 Hz
Measurement point: Ground surface 20 cm away from the unit leg
Installation condition: Direct installation on the concrete floor
Power source: 3-phase 4-wire 380-400
-415 V 50/60 Hz
Operation condition: JIS condition (cooling, heating)
Measurement device: Vibration level meter for vibration pollution VM-1220C (JIS-compliant product)
Vibration level
Model
Vibration level (dB)
PUHY-P200YKB-A1 (-BS)
45
PUHY-P250YKB-A1 (-BS)
46
PUHY-P300YKB-A1 (-BS)
47
PUHY-P350YKB-A1 (-BS)
47
PUHY-P400YKB-A1 (-BS)
47
PUHY-P450YKB-A1 (-BS)
47
PUHY-P500YKB-A1 (-BS)
48
PUHY-P400YSKB-A1 (-BS)
48
PUHY-P450YSKB-A1 (-BS)
48.5
PUHY-P500YSKB-A1 (-BS)
49
PUHY-P550YSKB-A1 (-BS)
49.5
PUHY-P600YSKB-A1 (-BS)
49.5
PUHY-P650YSKB-A1 (-BS)
50
PUHY-P700YSKB-A1 (-BS)
50
PUHY-P750YSKB-A1 (-BS)
50
PUHY-P800YSKB-A1 (-BS)
50
PUHY-P850YSKB-A1 (-BS)
50
PUHY-P900YSKB-A1 (-BS)
50
PUHY-P950YSKB-A1 (-BS)
51.5
PUHY-P1000YSKB-A1 (-BS)
52
PUHY-P1050YSKB-A1 (-BS)
52
PUHY-P1100YSKB-A1 (-BS)
52
PUHY-P1150YSKB-A1 (-BS)
52
PUHY-P1200YSKB-A1 (-BS)
52
PUHY-P1250YSKB-A1 (-BS)
52
PUHY-P1300YSKB-A1 (-BS)
52
PUHY-P1350YSKB-A1 (-BS)
52