1 .. 351 352 353 354 355 356 357 358 359 360 361 .. 908
2 - 51
Y
MEE15K022
5. SOUND LEVELS
YKB/YLM 2nd
5. SOUND LEVELS
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.
Measurement
location
1m
1m
Measurement condition
PUHY-P200, 250YKB-A1(-BS)
Measurement
location
1m
1m
Measurement condition
PUHY-P300, 350, 400YKB-A1(-BS)
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
72.0
63.0
60.0
55.0
48.5
44.0
38.5
33.0
57.0
Low noise mode
50/60Hz
56.5
54.0
45.5
41.5
36.5
28.0
25.5
22.5
44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
125
250
500
1k
2k
4k
8k
NC
-40
NC
-30
NC
-20
NC
-60
NC
-50
NC
-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand
50/60Hz
Low
50/60Hz
Sound level of PUHY-P200YKB-A1(-BS)
63
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
77.0
69.0
63.0
59.0
52.5
46.5
41.0
35.0
61.0
Low noise mode
50/60Hz
68.0
60.5
52.5
47.0
41.5
41.0
30.0
31.0
51.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
125
250
500
1k
2k
4k
8k
NC
-40
NC
-30
NC
-20
NC
-60
NC
-50
NC
-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand
50/60Hz
Low
50/60Hz
Sound level of PUHY-P300YKB-A1(-BS)
63
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
74.5
65.0
62.0
57.0
50.0
46.0
41.5
37.5
59.0
Low noise mode
50/60Hz
61.5
60.0
47.0
45.5
38.5
30.5
28.5
25.5
48.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
125
250
500
1k
2k
4k
8k
NC
-40
NC
-30
NC
-20
NC
-60
NC
-50
NC
-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand
50/60Hz
Low
50/60Hz
Sound level of PUHY-P250YKB-A1(-BS)
63
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
77.5
67.5
63.5
59.0
52.5
47.0
41.0
36.0
61.0
Low noise mode
50/60Hz
71.0
59.0
50.0
45.5
41.0
43.5
31.0
31.5
51.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
125
250
500
1k
2k
4k
8k
NC
-40
NC
-30
NC
-20
NC
-60
NC
-50
NC
-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand
50/60Hz
Low
50/60Hz
Sound level of PUHY-P350YKB-A1(-BS)
63