1 - 295
CT
MEE15K022
9. Heating [All indoor units]
YKB/YLM 2nd
9-4. Heating capacity with PUHY-P700-800YSKB-A1, EP700-800YSLM-A1
9-5. Heating capacity with PUHY-P850-1350YSKB-A1, EP850-1350YSLM-A1
9-6. Heating capacity with PURY-(E)P200-250YLM-A1
All indoor units
SHC: Sensible Heat Capacity (kW)
Model
size
(Rated kW)
Indoor air temp.
15°C D.B.
20°C D.
B.
25°C D.B.
27°C D.B.
SHC
SHC
SHC
SHC
15 (1.9)
1.9
1.9
1.5
1.3
20 (2.5)
2.5
2.5
2.0
1.8
25 (3.2)
3.2
3.2
2.6
2.2
32 (4.0)
4.0
4.0
3.2
2.8
40 (5.0)
5.1
5.0
4.0
3.5
50 (6.3)
6.4
6.3
5.0
4.4
63 (8.0)
8.1
8.0
6.4
5.6
71 (9.0)
9.1
9.0
7.2
6.3
80 (10.0)
10.1
10.0
8.0
7.0
100 (12.5)
12.6
12.5
10.0
8.7
125 (16.0)
16.2
16.0
12.8
11.2
140 (18.0)
18.2
18.0
14.4
12.6
200 (25.0)
25.3
25.0
20.0
17.5
250 (31.5)
31.8
31.5
25.2
22.1
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
All indoor units
SHC: Sensible Heat Capacity (kW)
Model
size
(Rated kW)
Indoor air temp.
15°C D.B.
20°C D.
B.
25°C D.B.
27°C D.B.
SHC
SHC
SHC
SHC
15 (1.9)
1.9
1.9
1.4
1.2
20 (2.5)
2.6
2.5
1.9
1.6
25 (3.2)
3.3
3.2
2.4
2.0
32 (4.0)
4.1
4.0
3.0
2.6
40 (5.0)
5.1
5.0
3.7
3.2
50 (6.3)
6.5
6.3
4.7
4.0
63 (8.0)
8.2
8.0
6.0
5.1
71 (9.0)
9.2
9.0
6.7
5.8
80 (10.0)
10.2
10.0
7.5
6.4
100 (12.5)
12.8
12.5
9.3
8.0
125 (16.0)
16.4
16.0
11.9
10.2
140 (18.0)
18.4
18.0
13.4
11.5
200 (25.0)
25.6
25.0
18.6
16.0
250 (31.5)
32.3
31.5
23.5
20.2
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
All indoor units
SHC: Sensible Heat Capacity (kW)
Model
size
(Rated kW)
Indoor air temp.
15°C D.B.
20°C D.
B.
25°C D.B.
27°C D.B.
SHC
SHC
SHC
SHC
15 (1.9)
1.9
1.9
1.5
1.3
20 (2.5)
2.5
2.5
2.0
1.8
25 (3.2)
3.2
3.2
2.6
2.2
32 (4.0)
4.0
4.0
3.2
2.8
40 (5.0)
5.1
5.0
4.0
3.5
50 (6.3)
6.4
6.3
5.0
4.4
63 (8.0)
8.1
8.0
6.4
5.6
71 (9.0)
9.1
9.0
7.2
6.3
80 (10.0)
10.1
10.0
8.0
7.0
100 (12.5)
12.6
12.5
10.0
8.7
125 (16.0)
16.2
16.0
12.8
11.2
140 (18.0)
18.2
18.0
14.4
12.6
200 (25.0)
25.3
25.0
20.0
17.5
250 (31.5)
31.8
31.5
25.2
22.1
* The capacity does not depend on the outdoor temperature.