1 .. 254 255 256 257 258 259 260 261 262 263 264 .. 908
1 - 254
CT
MEE15K022
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
YKB/YLM 2nd
I.
CAPACITY TABLES
1. Cooling   [Ceiling concealed (Silent/Slim/High static pressure type)]
1-1. Cooling capacity with PUHY-P200-250YKB-A1, EP200-250YLM-A1
1-2. Cooling capacity with PUHY-P300-400YKB-A1, EP300-350YLM-A1
PEFY-P-VMR-E-L/R
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
20 (2.2)
2.0
1.7
2.0
1.7
2.2
1.7
2.2
1.8
2.3
1.8
2.4
1.8
2.6
1.8
25 (2.8)
2.5
1.9
2.6
2.0
2.8
2.0
2.8
2.1
2.9
2.1
3.1
2.0
3.2
2.0
32 (3.6)
3.2
2.3
3.3
2.4
3.5
2.4
3.6
2.5
3.7
2.5
3.9
2.4
4.2
2.4
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PEFY-P-VMS1(L)-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
15 (1.7)
1.5
1.4
1.6
1.5
1.7
1.5
1.7
1.6
1.8
1.6
1.9
1.6
2.0
1.5
20 (2.2)
2.0
1.7
2.0
1.8
2.2
1.8
2.2
1.9
2.3
1.9
2.4
1.9
2.6
1.8
25 (2.8)
2.5
2.1
2.6
2.1
2.8
2.1
2.8
2.2
2.9
2.2
3.1
2.2
3.2
2.2
32 (3.6)
3.2
2.5
3.3
2.6
3.5
2.5
3.6
2.7
3.7
2.7
3.9
2.6
4.2
2.6
40 (4.5)
4.1
3.0
4.2
3.1
4.4
3.1
4.5
3.2
4.7
3.2
4.9
3.2
5.2
3.1
50 (5.6)
5.0
3.7
5.2
3.8
5.5
3.8
5.6
4.0
5.8
4.0
6.1
3.9
6.5
3.8
63 (7.1)
6.4
4.7
6.6
4.8
7.0
4.8
7.1
5.0
7.4
5.0
7.8
4.9
8.2
4.8
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PEFY-P-VMH-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
40 (4.5)
4.1
3.1
4.2
3.2
4.4
3.2
4.5
3.4
4.7
3.4
4.9
3.3
5.2
3.3
50 (5.6)
5.0
3.7
5.2
3.8
5.5
3.7
5.6
3.9
5.8
3.9
6.1
3.8
6.5
3.8
63 (7.1)
6.4
4.8
6.6
5.0
7.0
4.9
7.1
5.2
7.4
5.2
7.8
5.1
8.2
5.0
71 (8.0)
7.2
5.4
7.4
5.6
7.9
5.5
8.0
5.8
8.3
5.8
8.7
5.7
9.3
5.6
80 (9.0)
8.1
6.1
8.4
6.3
8.9
6.2
9.0
6.5
9.3
6.5
9.8
6.4
10.4
6.3
100 (11.2)
10.1
8.3
10.4
8.5
11.0
8.4
11.2
9.0
11.6
8.9
12.2
8.8
13.0
8.7
125 (14.0)
12.6
9.5
13.0
9.8
13.8
9.7
14.0
10.1
14.5
10.1
15.3
10.0
16.2
9.8
1
4
0
(
1
6
.
0
)
1
4
.
4
1
0
.
8
1
4
.
9
1
1
.
2
1
5
.
7
1
1
.
0
1
6
.
0
1
1
.
6
1
6
.
6
1
1
.
6
1
7
.
5
1
1
.
4
1
8
.
6
1
1
.
2
2
0
0
(
2
2
.
4
)
2
0
.
2
1
5
.
6
2
0
.
8
1
6
.
0
2
2
.
0
1
5
.
8
2
2
.
4
1
6
.
7
2
3
.
3
1
6
.
7
2
4
.
5
1
6
.
4
2
6
.
0
1
6
.
2
2
5
0
(
2
8
.
0
)
2
5
.
2
1
9
.
3
2
6
.
0
1
9
.
9
2
7
.
5
1
9
.
7
2
8
.
0
2
0
.
7
2
9
.
1
2
0
.
7
3
0
.
6
2
0
.
4
3
2
.
5
2
0
.
1
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PEFY-P-VMHS-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
2
0
0
(
2
2
.
4
)
2
0
.
2
1
6
.
8
2
0
.
8
1
7
.
4
2
2
.
0
1
7
.
2
2
2
.
4
1
8
.
3
2
3
.
3
1
8
.
3
2
4
.
5
1
8
.
0
2
6
.
0
1
7
.
8
2
5
0
(
2
8
.
0
)
2
5
.
2
2
0
.
5
2
6
.
0
2
1
.
2
2
7
.
5
2
1
.
0
2
8
.
0
2
2
.
3
2
9
.
1
2
2
.
2
3
0
.
6
2
1
.
8
3
2
.
5
2
1
.
6
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PEFY-P-VMR-E-L/R
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
20 (2.2)
2.0
1.7
2.0
1.7
2.2
1.7
2.2
1.8
2.3
1.8
2.4
1.8
2.6
1.8
25 (2.8)
2.5
1.9
2.6
2.0
2.8
2.0
2.8
2.1
2.9
2.1
3.1
2.0
3.2
2.0
32 (3.6)
3.2
2.3
3.3
2.4
3.5
2.4
3.6
2.5
3.7
2.5
3.9
2.4
4.2
2.4
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412