2. EXTERNAL DIMENSIONS
YKB/YLM 2nd
1 - 140
PLFY-VC
M/VBM
MEE15K022
Ceiling
Cut out hole
Burring hole pitch
3-
ø
2.8
Burring hole
Detail drawing of fresh air intake hole
Burring hole
14-
ø
2.8
Cut out hole
Burring hole pitch
Cut out hole
Detail connecting of Branch duct (Both aspects)
PLFY
-P20, 25, 32, 40, 50, 63, 80, 100, 125VBM-E
Unit: mm
100
130
350
90
100
100
90
70
°
* 167
* 155
ø
150
ø
175
*
ø
125
ø
100
158
120
°
120
°
377
284
60
In case of Auto-Grille : PLP-6BAJ
In case of wireless remote controller : PLP-6BALM
In case of standard grille : PLP-6BA
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
Power supply wire,
Indoor unit/Outdoor unit
connecting wire entry
Transmission terminal block
Emergency operation switch <Cooling>
and Emergency Up/Down switch <Up>
Emergency operation
switch <Heating> and
Emergency Up/Down switch <Down>
Control wire entry
Suspension bolt
lower edge
Vane motor
Air intake
grille
Air outlet hole
Air outlet hole
 Auto vane
(Air outlet)
Air intake hole
Air intake hole
Grille
Ceiling
Keep approximatety
10 to 15 mm space
between unit ceilling
and ceilling slab.
Suspension bolt
M10 or W3/8
Branch duct hole
Fresh air
intake hole
Branch duct hole
Ceiling hole
Suspension bolt pitch
Suspension bolt pitch
Ceiling hole
(7.5)
(7.5)
605
620
DEFROST/STAND BY lamp
Receiver
Operation lamp
For MA-Remote controller
terminal block
160
160
1
2
500
500
597
M
M
M
M
83
36
950
83
36
950
597
*
50~70
* 140
* 170
35
17
+5
0
* 105
* 156
* 190
A
* B
160
840
150
90
C
D
840
187.5
20~45
860~910
20~45
810
20~45
860~910
20~45
24
160
Power supply
terminal block
)
(
Connected the attached
flexible pipe or socket.
I.D. 32 (1-1/4")
Drain pipe
PVC pipe: O.D. 32 (1-1/4")
 
Note  1.
Please choose the Grille from a standard grille, Auto-Grille.
 
2.
As for drain pipe, please use VP-25 (O.D. ø32 PVC TUBE).
 
 
Drain pump inclusion.
 
 
Raise is max 850mm from the ceiling.
 
3.
As for suspension bolt, please use M10 or W3/8. (Procured at local site)
 
4.
Electrical box may be removed for the service purpose.
 
 
Make sure to slack the electrical wire little bit for control/power wires connection.
 
5.
The height of the indoor unit is able to be adjusted with the grille attached.
 
6.
For the installation of the optional high efficiency filter or optional
multi-functional
casement.
 
 
1) Requires E or more space between transom and ceiling for the installation.
 
 
2) Add 135 mm to the dimensions * marked on the figure.
 
 
3) The optional high efficiency filter becomes optional multi-functional
 
 
 
casement and concomitant use.
 
7.  
When installing the branch ducts, be sure to insulate adequately.
 
 
Otherwise condensation and dripping may occur.
 
 
(It becomes the cause of dew drops/Wear dew.)
  
8.  
As for necessary installation/service space, please refer to the left at figure.    
87
74
81
77
298
241
258
80
85
78
281
Refrigerant pipe
ø15.88
Flared connection
5/8F
D
400
440
E
C
B
A
Refrigerant pipe
ø12.7
Flared connection
1/2F
Refrigerant pipe···ø15.88  
Flared connection···5/8F  
Refrigerant pipe ···ø12.7  
Flared connection···1/2F  
Refrigerant pipe···ø 6.35  
Flared connection···1/4F  
Refrigerant pipe
  ø6.35 /ø9.52
Flared connection
1/4F / 3/8F (compatible)
PLFY-P50VBM-E
PLFY-P63,80VBM-E
PLFY-P100,125VBM-E
Refrigerant pipe···3/8F
Flared connection···ø9.52    
Models
PLFY-P20,25,32,40VBM-E
2
1
Accessory ··· Drain socket (I.D. 32 (1-1/4"))
1000 mm
or more
3000 mm or
more
Indoor unit
Indoor unit
Floor
Obstacle
1500 mm
or more
Grille
Ceiling
For high
attachment
2500mm or more
from floor
Ceiling
Air intake grille
L.L Filter
Auto-Grille
Max. 4.0m
Air intake grille Up/down distance